14.24
IED status for IEC 60870-5-103 I103IED
14.24.1
Functionality
I103IED is a function block with defined IED functions in monitor direction. This block
uses parameter as
FunctionType
, and information number parameter is defined for each
input signal.
14.24.2
Function block
I103IED
BLOCK
19_LEDRS
21_TESTM
22_SETCH
23_GRP1
24_GRP2
25_GRP3
26_GRP4
IEC10000292-2-en.vsd
IEC10000292 V2 EN
Figure 329:
I103IED function block
14.24.3
Signals
Table 525:
I103IED Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
19_LEDRS
BOOLEAN
0
Information number 19, reset LEDs
21_TESTM
BOOLEAN
0
Information number 21, test mode is active
22_SETCH
BOOLEAN
0
Information number 22, setting changed
23_GRP1
BOOLEAN
0
Information number 23, setting group 1 is active
24_GRP2
BOOLEAN
0
Information number 24, setting group 2 is active
25_GRP3
BOOLEAN
0
Information number 25, setting group 3 is active
26_GRP4
BOOLEAN
0
Information number 26, setting group 4 is active
14.24.4
Settings
Table 526:
I103IED Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
1MRK 506 335-UUS A
Section 14
Monitoring
703
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...