Spring charge time measurement
Two binary inputs,
SPRCHRGN
and
SPRCHRGD
, indicate spring charging started and
spring charged, respectively. The spring charging time is calculated from the difference of
these two signal timings.
The spring charging time
SPRCHRT
is available through the Monitored data view .
Alarm limit check
If the time taken by the spring to charge is more than the value set with the
tSprngChrgAlm
setting, the subfunction generates the
SPRCHRAL
alarm.
It is possible to block the
SPRCHRAL
alarm signal by activating the
BLOCK
binary input.
14.18.7.8
Gas pressure supervision
The gas pressure supervision subfunction monitors the gas pressure inside the arc
chamber.
The operation of the subfunction can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
ALMPRES
LOPRES
PRESLO
PRESALM
BLOCK
BLK_ALM
0
0-tPressAlm
0
0-TPressLO
ANSI11000293-1-en.vsd
ANSI11000293 V1 EN
Figure 322:
Functional module diagram for circuit breaker gas pressure alarm
The gas pressure is monitored through the binary input signals
LOPRES
and
ALMPRES
.
Pressure alarm time delay
When the
ALMPRES
binary input is activated, the
PRESALM
alarm is activated after a
time delay set with the
tPressAlm
setting. The
PRESALM
alarm can be blocked by
activating the
BLOCK
input.
If the pressure drops further to a very low level, the
LOPRES
binary input becomes high,
activating the lockout alarm
PRESLO
after a time delay set with the
TPressLO
setting. The
PRESLO
alarm can be blocked by activating the
BLOCK
input.
1MRK 506 335-UUS A
Section 14
Monitoring
693
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...