![ABB REL650 series Скачать руководство пользователя страница 698](http://html.mh-extra.com/html/abb/rel650-series/rel650-series_technical-manual_4784698.webp)
The remaining life is calculated separately for all three phases and it is available as a
monitored data value
CBLIFE_A (_B, _C)
. The values can be cleared by setting the
parameter
CB wear values
in the clear menu from LHMI.
Clearing
CB wear values
also resets the operation counter.
Alarm limit check
When the remaining life of any phase drops below the
LifeAlmLevel
threshold setting, the
corresponding circuit breaker life alarm
CBLIFEAL
is activated.
It is possible to deactivate the
CBLIFEAL
alarm signal by activating the binary input
BLOCK
. The old circuit breaker operation counter value can be taken into use by writing
the value to the
Initial CB Rmn life
parameter and resetting the value via the clear menu
from LHMI.
It is possible to deactivate the
CBLIFEAL
alarm signal by activating the binary input
BLOCK
.
14.18.7.7
Circuit breaker spring charged indication
The circuit breaker spring charged indication subfunction calculates the spring charging
time.
The operation of the subfunction can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
GUID-37EB9FAE-8129-45AB-B9F7-7F7DC829E3ED V1 EN
Figure 321:
Functional module diagram for circuit breaker spring charged indication
and alarm
Section 14
1MRK 506 335-UUS A
Monitoring
692
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...