GUID-82C88B52-1812-477F-8B1A-3011A300547A V1 EN
Figure 315:
Functional module diagram for calculating inactive days and alarm for
circuit breaker operation monitoring
Inactivity timer
The module calculates the number of days the circuit breaker has remained inactive, that
is, has stayed in the same open or closed state. The calculation is done by monitoring the
states of the
POSOPEN
and
POSCLOSE
auxiliary contacts.
The inactive days
NOOPRDAY
is available through the Monitored data view. It is also
possible to set the initial inactive days by using the
InactDayInit
parameter.
Alarm limit check
When the inactive days exceed the limit value defined with the
InactDayAlm
setting, the
NOOPRALM
alarm is initiated. The time in hours at which this alarm is activated can be set
with the
InactHourAlm
parameter as coordinates of UTC. The alarm signal
NOOPRALM
can be blocked by activating the binary input
BLOCK
.
14.18.7.3
Breaker contact travel time
The breaker contact travel time module calculates the breaker contact travel time for the
closing and opening operation. The operation of the breaker contact travel time
measurement can be described by using a module diagram. All the modules in the diagram
are explained in the next sections.
GUID-4D82C157-53AF-40C9-861C-CF131B49072B V1 EN
Figure 316:
Functional module diagram for breaker contact travel time
1MRK 506 335-UUS A
Section 14
Monitoring
687
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...