with recorded load (pre-fault) currents, is used to exactly calculate the fault position. The
fault can be recalculated with new source data at the actual fault to further increase the
accuracy.
Especially on heavily loaded long lines, where the source voltage angles can be up to
35-40 degrees apart, the accuracy can be still maintained with the advanced compensation
included in fault locator.
14.14.3
Function block
ANSI09000621-2-en.vsd
LMBRFLO
PHSEL_A*
PHSEL_B*
PHSEL_C*
CALCDIST*
CALCMADE
FLTDISTX
BCD_80
BCD_40
BCD_20
BCD_10
BCD_8
BCD_4
BCD_2
BCD_1
ANSI09000621 V2 EN
Figure 305:
LMBRFLO function block
14.14.4
Signals
Table 489:
LMBRFLO Input signals
Name
Type
Default
Description
PHSEL_A
BOOLEAN
0
Phase selection phase A
PHSEL_B
BOOLEAN
0
Phase selection phase B
PHSEL_C
BOOLEAN
0
Phase selection phase C
CALCDIST
BOOLEAN
0
Input signal to initiate fault distance calculation
Table 490:
LMBRFLO Output signals
Name
Type
Description
CALCMADE
BOOLEAN
Fault calculation made
FLT_X
REAL
Reactive distance to fault
BCD_80
BOOLEAN
Distance in binary coded data, bit represents 80%
BCD_40
BOOLEAN
Distance in binary coded data, bit represents 40%
BCD_20
BOOLEAN
Distance in binary coded data, bit represents 20%
BCD_10
BOOLEAN
Distance in binary coded data, bit represents 10%
Table continues on next page
1MRK 506 335-UUS A
Section 14
Monitoring
663
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...