14.9.6
Technical data
Table 478:
DRPRDRE technical data
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
96
Maximum number of disturbance reports
100
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
340 seconds (100
recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz
14.10
IEC 61850 generic communication I/O functions
SPGGIO
14.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
SPGGIO
-
-
14.10.2
Functionality
IEC61850 generic communication I/O functions SPGGIO is used to send one single
logical signal to other systems or equipment in the substation.
14.10.3
Function block
SPGGIO
BLOCK
^IN
IEC09000237_en_1.vsd
IEC09000237 V1 EN
Figure 302:
SPGGIO function block