EXACC
BOOLEAN
0
Connected to function used for tripping at zone
extension
BC
BOOLEAN
0
Breaker Close
LLACC
BOOLEAN
0
Connected to function used for tripping at loss of load
Table 348:
ZCLCPLAL Output signals
Name
Type
Description
TRZE
BOOLEAN
Trip by zone extension
TRLL
BOOLEAN
Trip by loss of load
12.4.5
Settings
Table 349:
ZCLCPLAL Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
LoadCurr
1 - 100
%IB
1
10
Load current before disturbance in % of IBase
LossOfLoad
Disabled
Enabled
-
-
Disabled
Enable/Disable operation of Loss of load
ZoneExtension
Disabled
Enabled
-
-
Disabled
Enable/Disable operation of Zone extension
MinCurr
1 - 100
%IB
1
5
Level taken as current loss due to remote CB
trip in % of IBase
tLowCurr
0.000 - 60.000
s
0.001
0.200
Time delay on pick-up for MINCURR value
tLoadOn
0.000 - 60.000
s
0.001
0.000
Time delay on pick-up for load current release
tLoadOff
0.000 - 60.000
s
0.001
0.300
Time delay on drop off for load current release
Table 350:
ZCLCPLAL Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Section 12
1MRK 506 335-UUS A
Scheme communication
514
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...