11.4.2.5
Settings
Table 255:
SCSWI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CtlModel
Dir Norm
SBO Enh
-
-
SBO Enh
Specifies control model type
PosDependent
Always permitted
Not perm at 00/11
-
-
Always permitted
Permission to operate depending on the
position
tSelect
0.000 - 60.000
s
0.001
30.000
Maximum time between select and execute
signals
tSynchrocheck
0.00 - 600.00
s
0.01
10.00
Allowed time for synchronism-check to fulfil
close conditions
tSynchronizing
0.00 - 600.00
s
0.01
0.00
Supervision time to get the signal
synchronizing in progress
tExecutionFB
0.00 - 600.00
s
0.01
30.00
Maximum time from command execution to
termination
11.4.3
Circuit breaker SXCBR
11.4.3.1
Signals
Table 256:
SXCBR Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
LR_SWI
BOOLEAN
0
Local/Remote switch indication from switchyard
OPEN
BOOLEAN
0
Pulsed signal used to immediately open the switch
CLOSE
BOOLEAN
0
Pulsed signal used to immediately close the switch
BL_OPEN
BOOLEAN
0
Signal to block the open command
BL_CLOSE
BOOLEAN
0
Signal to block the close command
BL_UPD
BOOLEAN
0
Steady signal for block of the position updating
POSOPEN
BOOLEAN
0
Signal for open position of apparatus from I/O
POSCLOSE
BOOLEAN
0
Signal for close position of apparatus from I/O
TR_OPEN
BOOLEAN
0
Signal for open position of truck from I/O
TR_CLOSE
BOOLEAN
0
Signal for close position of truck from I/O
RS_CNT
BOOLEAN
0
Resets the operation counter
XIN
BOOLEAN
0
Execution information from CSWI
Section 11
1MRK 506 335-UUS A
Control
392
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...