11.3.7
Technical data
Table 252:
STBRREC (79) technical data
Function
Range or value
Accuracy
Number of autoreclosing shots
1-5
-
Autoreclosing open time:
Shot 1 - t1 3Ph
Shot 1 - t1 1Ph
(0.000-60.000) s
± 0.5% ± 25 ms
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
(0.00-6000.00) s
Autorecloser maximum wait time
for sync
(0.00-6000.00) s
Open time extension for long trip
time
(0.000-60.000) s
Maximum trip pulse duration
(0.000-60.000) s
Inhibit reset time
(0.000-60.000) s
Reset time
(0.00-6000.00) s
Minimum time CB must be closed
before AR becomes ready for
autoreclosing cycle
(0.00-6000.00) s
CB check time before
unsuccessful
(0.00-6000.00) s
Wait for master release
(0.00-6000.00) s
Wait time after close command
before proceeding to next shot
(0.000-60.000) s
11.4
Apparatus control
11.4.1
Functionality
The apparatus control function APC8 for up to 8 apparatuses is used for control and
supervision of circuit breakers, disconnectors and grounding switches within a bay.
Permission to operate is given after evaluation of conditions from other functions such as
interlocking, synchronism check, operator place selection and external or internal
blockings.
In normal security, the command is processed and the resulting position is not supervised.
However with enhanced security, the command is processed and the resulting position is
supervised.
1MRK 506 335-UUS A
Section 11
Control
389
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...