11.2.7
Technical data
Table 247:
SMBRREC (79) technical data
Function
Range or value
Accuracy
Number of autoreclosing shots
1 - 5
-
Autoreclosing open time:
shot 1 - t1 3Ph
(0.000-60.000) s
± 0.5% ± 25 ms
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
(0.00-6000.00) s
Autorecloser maximum wait time for sync
(0.00-6000.00) s
Maximum trip pulse duration
(0.000-60.000) s
Inhibit reset time
(0.000-60.000) s
Reset time
(0.00-6000.00) s
Minimum time CB must be closed before AR
becomes ready for autoreclosing cycle
(0.00-6000.00) s
CB check time before unsuccessful
(0.00-6000.00) s
Wait for master release
(0.00-6000.00) s
Wait time after close command before proceeding
to next shot
(0.000-60.000) s
11.3
Autorecloser for 1/3-phase operation STBRREC (79)
11.3.1
Identification
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Autorecloser for 1/3-phase operation
STBRREC
O->I
SYMBOL-L V1 EN
79
11.3.2
Functionality
The autoreclosing function provides high-speed and/or delayed auto-reclosing for single
breaker applications.
1MRK 506 335-UUS A
Section 11
Control
375
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...