Two step overvoltage protection (OV2PTOV, 59) function can be used to detect open line
ends, normally then combined with a directional reactive over-power function to
supervise the system voltage. When triggered, the function will cause an alarm, switch in
reactors, or switch out capacitor banks.
OV2PTOV (59) has two voltage steps, where step 1 can be set as inverse or definite time
delayed. Step 2 is always definite time delayed.
OV2PTOV (59) has a high reset ratio to allow settings close to system service voltage.
8.2.3
Function block
ANSI09000278-1-en.vsd
OV2PTOV (59)
V3P*
BLOCK
BLK1
BLK2
TRIP
TRST1
TRST2
PICKUP
PU_ST1
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2
ANSI09000278 V1 EN
Figure 139:
OV2PTOV function block (59)
8.2.4
Signals
Table 189:
OV2PTOV (59) Input signals
Name
Type
Default
Description
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLK1
BOOLEAN
0
Block of step 1
BLK2
BOOLEAN
0
Block of step 2
Table 190:
OV2PTOV (59) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
TRST1
BOOLEAN
Trip signal from step 1
TRST2
BOOLEAN
Trip signal from step 2
PICKUP
BOOLEAN
General pickup signal
PU_ST1
BOOLEAN
Start signal from step 1
Table continues on next page
Section 8
1MRK 506 335-UUS A
Voltage protection
300
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...