![ABB REL650 series Скачать руководство пользователя страница 273](http://html.mh-extra.com/html/abb/rel650-series/rel650-series_technical-manual_4784273.webp)
ANSI16000503-1-en.vsd
BFP Started A
AND
BFP Started B
BFP Started C
From other
phases
OR
OR
AND
AND
a
b
a>b
IN
IN>
1 out of 4
AND
OR
1 out of 3
Current High B
Current High C
From other
phases
AND
Current High A
OR
Contact Closed A
OR
Backup Trip A
200 ms
Backup Trip B
OR
From other
phases
Backup Trip C
TRBU
OR
2 out of 4
BUTripMode
1
AND
OR
Current High A
BFP Started A
30 ms
Backup Time Out A
AND
AND
AND
OR
OR
0
0-t2
0
60 s
ANSI16000503 V1 EN
Figure 124:
Simplified logic scheme of the back-up trip function
Internal logical signals Current High A, Current High B, and Current High C have logical
value 1 when current in respective phase has magnitude larger than setting parameter
Pickup_PH
.
7.11.8
Technical data
Table 144:
CSPRBRF (50BF) technical data
Function
Range or value
Accuracy
Operate phase current
(5-200)% of
lBase
±
1.0% of I
n
at I
£
I
n
±
1.0% of I at I > I
n
Reset ratio, phase current > 95%
-
Operate residual current
(2-200)% of
lBase
±
1.0% of I
n
at I
£
I
n
±
1.0% of I at I > I
n
Reset ratio, residual
current
> 95%
-
Phase current pickup for
blocking of contact
function
(5-200)% of
lBase
±
1.0% of I
n
at I
£
I
n
±
1.0% of I at I > I
n
Table continues on next page
1MRK 506 335-UUS A
Section 7
Current protection
267
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...