6.5.4
Signals
Table 49:
ZDNRDIR (21D) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
V3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
Table 50:
ZDNRDIR (21D) Output signals
Name
Type
Description
DIR_POL
GROUP SIGNAL
Polarizing voltage output for Mho
STDIRCND
INTEGER
Binary coded directional information per measuring loop
6.5.5
Settings
Table 51:
ZDNRDIR (21D) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
AngNegRes
90 - 175
Deg
1
115
Angle of blinder in second quadrant for forward
direction
AngDir
5 - 45
Deg
1
15
Angle of blinder in fourth quadrant for forward
direction
IMinPUPG
5 - 30
%IB
1
5
Minimum pickup phase current for Phase-to-
ground loops
IMinPUPP
5 - 30
%IB
1
10
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
Table 52:
ZDNRDIR (21D) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Section 6
1MRK 506 335-UUS A
Impedance protection
166
Technical manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 48: ...42 ...
Страница 58: ...52 ...
Страница 68: ...62 ...
Страница 74: ...68 ...
Страница 194: ...188 ...
Страница 534: ...528 ...
Страница 580: ...574 ...
Страница 722: ...716 ...
Страница 792: ...786 ...
Страница 855: ...849 ...