8=
-ABG
16=
-BCG
32=
-CAG
56=
-ABCG
8=
-AB
16=
-BC
32=
-CA
56=
ABC
The signal DLECND must be connected to the input LDCND for selected mho impedance
measuring zones ZMOPDIS.
In case several loops have to be released at the same time, the value is the sum of the values
for all loops, like the value for three-phase fault is the sum of the phase-to-phase loop
values (8+16+32=56).
6.3.7
Technical data
Table 42:
FMPSPDIS (21) technical data
Function
Range or value
Accuracy
Load encroachment criteria:
Load resistance, forward and
reverse
(1.00–3000)
W
/phase
(5–70) degrees
± 5.0% static accuracy
Conditions:
Voltage range: (0.1–1.1) x V
n
Current range: (0.5–30) x I
n
6.4
Additional distance protection directional function for
ground faults ZDARDIR (21D)
6.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Additional distance protection
directional function for ground faults
ZDARDIR
S00346 V1 EN
21D
Section 6
1MRK 506 335-UUS A
Impedance protection
160
Technical manual