X1OutRv
ZL
j
j
R
X
X1OutFw
X1InFw
1
RLdOutFw
RLdInFw
RLdOutRv
RLdInRv
2
3
4
X1InRv
IEC09000226_1_en.vsd
IEC09000226 V1 EN-US
Figure 14:
Operating principle and characteristic of the power swing detection
function (settings parameters in italic)
Where:
RLdInFw =
RLdOutFw · kLdRFw
RLdInRv =
RLdOutRv · kLdRRv
X1OutFw =
(RLdOutFw - RLdInFw)
X1OutRv =
(RLdOutFw - RLdInFw)
9.3.2.1
Verifying the settings
M13888-11 v6
Preconditions
The following output signal shall be configured to binary output available: ZOUT,
measured impedance within outer impedance boundary.
1MRK 506 383-UEN A
Section 9
Testing functionality by secondary injection
Line distance protection REL650 2.2 IEC
79
Commissioning manual
Содержание REL650 series
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Commissioning manual...
Страница 2: ......
Страница 24: ...18...
Страница 28: ...22...
Страница 38: ...32...
Страница 54: ...48...
Страница 58: ...52...
Страница 178: ...172...
Страница 182: ...176...
Страница 188: ...182...
Страница 196: ...190...
Страница 206: ...200...
Страница 207: ...201...