R
X
5
10
15
20
5
10
15
Line impedance
85 % of Line impedance
IEC09000410_1_en.vsd
IEC09000410 V1 EN
Figure 7:
Line impedance diagram
The setting
Z1
is calculated as:
,
1 0.85
0.85 2.5
17.5
15.0
Line posseq
Z
Z
j
=
×
=
×
+
=
W
GUID-B193DA37-6B3E-480E-80EE-0300427E4382 V1 EN
(Equation 5)
4.
Set
MhoCharZ1
to
Directional
.
This setting will be used if
CharPGZ1
and
CharPPZ1
is set to
Mho
.
If
CharPGZ1
or
CharPPZ1
is set as
Mho
then only Z1 setting will be
used.
RFPG1
and
RFPP1
will not have any effect.
5.
If
CharPPZ1
is selected as
Quadrilateral
then set
RFPP1
to
15 Ω
The fault resistance setting for phase-to-phase faults is normally the resistance arc
between the faulty phases. The fault resistance can approximately be calculated by
using the van Warrington expression:
L
I
R
arc
×
»
4
.
1
28700
GUID-F2E73133-F8B8-4594-BB6D-D9823E83F0E4 V1 EN
(Equation 6)
where:
•
I
is the arc current in A
•
L
is the length of the arc in m
The length of the arc is equal to the distance between the phases. For this line the
distance between the phases is 5 m.
The fault current for a phase-to-phase fault at the open line end and minimum short
circuit capacity is:
Section 3
1MRK 506 334-UUS A
REL650 setting examples
48
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...