![ABB REL650 series Скачать руководство пользователя страница 273](http://html1.mh-extra.com/html/abb/rel650-series/rel650-series_applications-manual_3479164273.webp)
8.4
Loss of voltage check LOVPTUV (27)
8.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Loss of voltage check
LOVPTUV
-
27
8.4.2
Application
The trip of the circuit breaker at a prolonged loss of voltage at all the three phases is
normally used in automatic restoration systems to facilitate the system restoration after a
major blackout. Loss of voltage check (LOVPTUV, 27) generates a TRIP signal only if
the voltage in all the three phases is low for more than the set time. If the trip to the circuit
breaker is not required, LOVPTUV (27) is used for signallization only through an output
contact or through the event recording function.
8.4.3
Setting guidelines
Loss of voltage check (LOVPTUV, 27) is in principle independent of the protection
functions. It requires to be set to open the circuit breaker in order to allow a simple system
restoration following a main voltage loss of a big part of the network and only when the
voltage is lost with breakers still closed.
GlobalBaseSel
: Selects the global base value group used by the function to define (
IBase
),
(
VBase
) and (
SBase
).
All settings are in primary values or per unit. Set operate level per phase to typically 70%
of the global parameter
VBase
level. Set the time delay
tTrip
=5-20 seconds.
8.4.4
Advanced users settings
For advanced users the following parameters need also to be set. Set the length of the trip
pulse to typical
tPulse
=0.15 sec. Set the blocking time
tBlock
to block Loss of voltage
check (LOVPTUV, 27), if some but not all voltage are low, to typical 5.0 seconds and set
the time delay for enabling the function after restoration
tRestore
to 3 - 40 seconds.
1MRK 506 334-UUS A
Section 8
Voltage protection
267
Application manual
Содержание REL650 series
Страница 1: ...Relion 650 series Line distance protection REL650 ANSI Application manual...
Страница 2: ......
Страница 30: ...24...
Страница 99: ...IED IED ANSI05000460 V2 EN 1MRK 506 334 UUS A Section 4 Analog inputs 93 Application manual...
Страница 110: ...104...
Страница 260: ...254...
Страница 274: ...268...
Страница 280: ...274...
Страница 396: ...390...
Страница 494: ...488...
Страница 506: ...500...
Страница 515: ...509...