30
Test menu
&KDSWHU
8QGHUV0,WUHH
7HVWPHQX
Use this menu to enable easier secondary injection tests of the REx 5xx terminal. It is
possible to block functions to prevent trip of circuit breakers and activation of alarm sig-
nals etc. to the control room during the testing activities.
The selectable modes, from the HMI, is the TestMode and ConfigMode.
TestMode:
•
Setting the terminal in test mode operation
•
Blocking of one or several protection and control functions (selectable) during test
operation.
•
Blocking of one or several event functions (selectable) during test operation.
•
Setting the disturbance report and the disturbance summary to On or Off during test
operation.
•
Special test mode to facilitate the testing of the line differential protection function.
This Diff. TestMode disables the trip-out from the remote terminal and enables test
from one end.
ConfigMode:
•
Setting the terminal in configuration mode operation. This will automatically be
done when down-loading a configuration from the CAP configuration tool. When
the down-loading is completed, the terminal automatically enters the normal mode.
Содержание REL 561*2.5
Страница 1: ...Operator s manual ProtectIT Line differential and distance protection terminal REL 561 2 5 ...
Страница 53: ...46 Test the LEDs of the LED module KDSWHU DQGOH WKH GLVWXUEDQFHV ...
Страница 77: ...70 Determine the active setting group KDSWHU 9LHZ WKH VHUYLFH UHSRUW ...
Страница 93: ...86 Retrieve the rated values of analog inputs KDSWHU 9LHZ WKH WHUPLQDO XQLW VWDWXV ...