Current reversal and weak end infeed
logic for distance protection (ZCAL)
Chapter 10
Verifying settings by secondary
injection
Change all settings cyclically for other faults (L2-N and L3-N).
Weak end infeed set for trip
1.
Apply input signals according table 4.
2.
Activate the carrier receive (ZCOM-CR or ZC1P-CRLn) signal
of the terminal.
3.
After the relay has operated, turn off the input signals.
4.
Check that trip, carrier-send signal, and indication are ob-
tained.
5.
Repeat the procedure for other phases.
Only when ZC1P is used.
Weak end infeed set for echo
1.
Apply input signals according table 4.
2.
Activate the carrier receive (ZCOM-CR or ZC1P-CRLn) signal
of the terminal.
3.
After the relay has operated turn off the input signals.
4.
Check that the carrier send signal is obtained.
5.
Repeat the procedure for other phases.
Only when ZC1P is used.
3.3
Completing the test
Continue to test another function or complete the test by setting the test mode to off.
Содержание REL 505-C1 2.3 Series
Страница 16: ...10 Note signs Chapter 2 Safety information ...
Страница 40: ...34 Checking the binary I O circuits Chapter 6 Checking the external circuitry ...
Страница 110: ...104 Two step time delayed phase overcurrent protection TOC2 Chapter 10 Verifying settings by secondary injection ...
Страница 114: ...108 Testing the interaction of the distance protection Chapter 11 Verifying the internal configuration ...