Power Automation and Protection Division
I.L. 40-201.9
REL 352 Version 1.00
I-9
I
A
P
P
E
N
D
I
X
The REL 352 should not trip.
9.
Out of Step System Functional Tests
For systems equipped with OST logic the following settings may be used to check the OST logic in REL 352:
NOTE:
These tests are optional and require programing Computer Aided, Multi-amp
or Doble test equipment.:
CA
Va = 35
∠
0
Vb = 69
∠
-120
Vc = 35
∠
+120
Ia = 4
∠
+75
Ib = 0
Ic = 4
∠
-105
PANG
=
65
GANG
=
65
ZR
=
3.0
BKUP
=
OUT
LOPB
=
NO
FDOP
=
IN
FDOG
=
IN
DIRU
=
ZSEQ
IOM
=
0.5
TOG
=
BLK
Z2P
=
8.5
T2P
=
0.1
Z2GF
=
6.5
Z2GR
=
0.01
T2G
=
0.1
Z3P
=
11.0
T3P
=
.2
Z3GF
=
11.0
Z3GR
=
0.01
T3G
=
.2
OST
=
WAYO
OSB
=
BOTH
RT
=
2.0
RU
=
4.0
OST1
=
2
OST2
=
3
OST3
=
3
OSOT
=
100
V (Volts)
I (Amps)
1
Va = 69
∠
0
Vb = 69
∠
-120
Vc = 69
∠
+120
Ia = 5
∠
-5
Ib = 5
∠
-125
Ic = 5
∠
+115
2
Va = 20
∠
0
Vb = 20
∠
-120
Vc = 20
∠
+120
Ia = 4.5
∠
-25
Ib = 4.5
∠
-145
Ic = 4.5
∠
+95
3
Va = 20
∠
0
Vb = 20
∠
-120
Vc = 20
∠
+120
Ia = 6
∠
-65
Ib = 6
∠
+175
Ic = 6
∠
+55
4
Va = 20
∠
0
Vb = 20
∠
-120
Vc = 20
∠
+120
Ia = 4
∠
-100
Ib = 4
∠
+140
Ic = 4
∠
+20
5
Va = 69
∠
0
Vb = 69
∠
-120
Vc = 69
∠
+120
Ia = 6.5
∠
-105
Ib = 6.5
∠
+135
Ic = 6.5
∠
+15
V
I
Содержание REL 352
Страница 2: ......
Страница 13: ...I L 40 201 9 Power Automation and Protection Division 1 6 REL 352 Version 1 00 Figure 1 1 REL 352 Front Panel ...
Страница 14: ...Power Automation and Protection Division I L 40 201 9 REL 352 Version 1 00 1 7 1 Figure 1 1a REL 352 Rear view ...
Страница 16: ......
Страница 130: ......