Power Automation and Protection Division
I.L. 40-201.9
REL 352 Version 1.00
1-5
1
c.
Power Up RAM Check
Immediately upon power-up, the relay does a complete ROM (EPROM) checksum of program
memory. Afterwards, the REL 352 relay continually computes the program memory checksum.
d. Nonvolatile RAM Check
All front-panel-entered constants (settings) are stored in nonvolatile RAM in three identical
arrays. These arrays are continuously checked by the program. If all three array entrees dis-
agree, a nonvolatile RAM failure is detected.
3.
UNIQUE REMOTE COMMUNICATION (WRELCOM) PROGRAM
Two optional types of remote interface can be ordered.
• RS232C for single point computer communication.
• INCOM for local network communication.
A special PC software (WRELCOM RCP and OSCAR) program are available for obtaining or
sending the setting information to the REL 352. The REL 352 front panel shows two fault
events (last and previous faults), but with the remote communication, 16 fault events and 3
records of oscillographic data can be obtained and stored. Each record of the oscillographic
data contains 8-cycle information (1-prefault and 7-post-fault), with 7 analog inputs and 24 dig-
ital data (at the sampling rate of 12 per cycle).