18.8.10.4
Signals
PID-3969-INPUTSIGNALS v5
Table 516:
I103CMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
PID-3969-OUTPUTSIGNALS v5
Table 517:
I103CMD Output signals
Name
Type
Description
16-AR
BOOLEAN
Information number 16, off/on of autorecloser
17-DIFF
BOOLEAN
Information number 17, block of differential
protection
18-PROT
BOOLEAN
Information number 18, block of protection
18.8.10.5
Settings
PID-3969-SETTINGS v5
Table 518:
I103CMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
18.8.11
IED commands for IEC 60870-5-103 I103IEDCMD
18.8.11.1
Functionality
GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5
I103IEDCMD is a command block in control direction with defined IED functions.
All outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
18.8.11.2
Identification
GUID-0D0B2477-1B0C-48F3-B047-CCF9C7A71856 v1
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED commands for IEC 60870-5-103
I103IEDCMD
-
-
1MRK 505 394-UEN A
Section 18
Station communication
Line differential protection RED650 2.2 IEC
721
Technical manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Technical manual...
Страница 2: ......
Страница 36: ...30...
Страница 46: ...40...
Страница 232: ...226...
Страница 272: ...266...
Страница 288: ...282...
Страница 306: ...300...
Страница 406: ...400...
Страница 436: ...430...
Страница 502: ...496...
Страница 614: ...608...
Страница 628: ...622...
Страница 644: ...638...
Страница 760: ...754...
Страница 778: ...772...
Страница 814: ...808...
Страница 870: ...864...
Страница 874: ...868...
Страница 924: ...918...
Страница 925: ...919...