L1
IL
1
IL
2
IL
3
L2
L3
Protected Object
IED
C
T
800
/1
in
D
e
lta
D
A
C
C
o
n
n
e
ct
e
d
IL3-IL2
IL2-IL1
IL1-IL3
2
3
4
IEC11000028-3-en.vsdx
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AI N
1
IEC11000028 V3 EN-US
Figure 14:
Delta DAC connected three-phase CT set
In this case, everything is done in a similar way as in the above described example,
except that for all used current inputs on the TRM the following setting parameters
shall be entered:
CT
prim
=800A
CT
sec
=1A
•
CTStarPoint
=ToObject
•
ConnectionType
=
Ph-Ph
It is important to notice the references in SMAI. As inputs at
Ph-Ph
are expected to
be L1L2, L2L3 respectively L3L1 we need to tilt 180º by setting
ToObject
.
4.2.2.7
Example how to connect single-phase CT to the IED
SEMOD55055-431 v8
Figure
gives an example how to connect the single-phase CT to the IED. It
gives an overview of the required actions by the user in order to make this
measurement available to the built-in protection and control functions within the
IED as well.
1MRK 505 393-UEN B
Section 4
Analog inputs
Line differential protection RED650 2.2 IEC
53
Application manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 32: ...26 ...
Страница 82: ...76 ...
Страница 112: ...106 ...
Страница 152: ...146 ...
Страница 208: ...202 ...
Страница 214: ...208 ...
Страница 282: ...276 ...
Страница 356: ...350 ...
Страница 404: ...398 ...
Страница 408: ...402 ...
Страница 442: ...436 ...
Страница 452: ...446 ...
Страница 453: ...447 ...