12.10.4
Signals
Table 396:
SPGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
IN
BOOLEAN
0
Input status
12.10.5
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
12.10.6
Operation principle
Upon receiving a signal at its input, IEC61850 generic communication I/O functions
(SPGGIO) function sends the signal over IEC 61850-8-1 to the equipment or system that
requests this signal. To get the signal, PCM600 must be used to define which function
block in which equipment or system should receive this information.
12.11
IEC 61850 generic communication I/O functions 16
inputs SP16GGIO
12.11.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions 16 inputs
SP16GGIO
-
-
12.11.2
Functionality
IEC 61850 generic communication I/O functions 16 inputs SP16GGIO function is used to
send up to 16 logical signals to other systems or equipment in the substation.
1MRK 511 287-UUS A
Section 12
Monitoring
499
Technical manual