12.4.2
Disturbance report DRPRDRE
12.4.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report
DRPRDRE
-
-
12.4.2.2
Function block
DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC09000346-1-en.vsd
IEC09000346 V1 EN
Figure 212:
DRPRDRE function block
12.4.2.3
Signals
Table 378:
DRPRDRE Output signals
Name
Type
Description
DRPOFF
BOOLEAN
Disturbance report function turned off
RECSTART
BOOLEAN
Disturbance recording started
RECMADE
BOOLEAN
Disturbance recording made
CLEARED
BOOLEAN
All disturbances in the disturbance report cleared
MEMUSED
BOOLEAN
More than 80% of memory used
12.4.2.4
Settings
Table 379:
DRPRDRE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Enable/Disable
PreFaultRecT
0.05 - 9.90
s
0.01
0.10
Pre-fault recording time
PostFaultRecT
0.1 - 10.0
s
0.1
0.5
Post-fault recording time
TimeLimit
0.5 - 10.0
s
0.1
1.0
Fault recording time limit
Table continues on next page
Section 12
1MRK 511 287-UUS A
Monitoring
458
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...