![ABB REC650 ANSI Скачать руководство пользователя страница 372](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772372.webp)
11.1.4
Signals
Table 256:
SMPPTRC (94) Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
TRINP_3P
BOOLEAN
0
Trip all phases
SETLKOUT
BOOLEAN
0
Input for setting the circuit breaker lockout function
RSTLKOUT
BOOLEAN
0
Input for resetting the circuit breaker lockout function
Table 257:
SMPPTRC (94) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
CLLKOUT
BOOLEAN
Circuit breaker lockout output (set until reset)
11.1.5
Settings
Table 258:
SMPPTRC (94) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Disable/Enable Operation
tTripMin
0.000 - 60.000
s
0.001
0.150
Minimum duration of trip output signal
Table 259:
SMPPTRC (94) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
TripLockout
Disabled
Enabled
-
-
Disabled
On: Activate output (CLLKOUT) and trip latch,
Off: Only output
AutoLock
Disabled
Enabled
-
-
Disabled
On: Lockout from input (SETLKOUT) and trip,
Off: Only input
11.1.6
Operation principle
The duration of a trip output signal from tripping logic common 3-phase output
SMPPTRC (94) is settable (
tTripMin
). The pulse length should be long enough to secure
the breaker opening.
For three-pole tripping logic common 3-phase output, SMPPTRC (94) has a single input
(TRINP_3P) through which all trip output signals from the protection functions within the
IED, or from external protection functions via one or more of the IEDs binary inputs, are
Section 11
1MRK 511 287-UUS A
Logic