![ABB REC650 ANSI Скачать руководство пользователя страница 261](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772261.webp)
Name
Type
Description
UPD_BLKD
BOOLEAN
Update of position indication is blocked
POSITION
INTEGER
Apparatus position indication
OPENPOS
BOOLEAN
Apparatus open position
CLOSEPOS
BOOLEAN
Apparatus closed position
TR_POS
INTEGER
Truck position indication
CNT_VAL
INTEGER
Operation counter value
L_CAUSE
INTEGER
Latest value of the error indication during command
10.3.4.5
Settings
Table 184:
SXSWI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
tStartMove
0.000 - 60.000
s
0.001
3.000
Supervision time for the apparatus to move
after a command
tIntermediate
0.000 - 60.000
s
0.001
15.000
Allowed time for intermediate position
AdaptivePulse
Not adaptive
Adaptive
-
-
Not adaptive
Output resets when a new correct end position
is reached
tOpenPulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for open command
tClosePulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for close command
SwitchType
Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
-
-
Disconnector
1=LoadBreak,2=Disconnector,3=GroundSw,
4=HighSpeedGroundSw
SuppressMidPos
Disabled
Enabled
-
-
Enabled
Mid-position is suppressed during the time
tIntermediate
10.3.5
Bay control QCBAY
10.3.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Bay control
QCBAY
-
-
1MRK 511 287-UUS A
Section 10
Control
255