-3V
0
=V
ref
RCA = 0
°
Operate area
Instrument
transformer
angle error
3I
0
(prim)
3I
0
(to prot)
a
Characteristic after
angle compensation
RCAcomp
en06000651_ansi.vsd
ANSI06000651 V1 EN
Figure 47:
Explanation of RCAComp
6.5.7.3
Directional residual power protection measuring 3I
0
· 3V
0
· cos φ
φ is defined as the angle between the residual current 3I
0
and the reference voltage
compensated with the set characteristic angle
RCADir
(φ=ang(3I
0
)—ang(V
ref
) ). V
ref
=
-3V
0
e
-jRCADir
. The function operates when 3I
0
· 3V
0
· cos φ gets larger than the set value.
For trip, both the residual power 3I
0
· 3V
0
· cos φ, the residual current 3I
0
and the release
voltage 3V
0
, shall be larger than the set levels (
SN_PU
,
INRelPU
and
VNRelPU
).
When the function is activated binary output signals PICKUP and PUDIRIN are activated.
If the output signals are active after the set delay
tDef
or after the inverse time delay
(setting
TDSN
) the binary output signals TRIP and TRDIRIN are activated.
The function shall indicate forward/reverse direction to the fault. Reverse direction is
defined as 3I
0
· 3V
0
·cos (φ + 180°)
³
the set value.
1MRK 511 287-UUS A
Section 6
Current protection
123
Technical manual