![ABB REC650 ANSI Скачать руководство пользователя страница 106](http://html.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_technical-manual_2772106.webp)
Table 44:
EF4PTOC Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
TR1
BOOLEAN
Trip signal from step 1
TR2
BOOLEAN
Trip signal from step 2
TR3
BOOLEAN
Trip signal from step 3
TR4
BOOLEAN
Trip signal from step 4
START
BOOLEAN
General start signal
ST1
BOOLEAN
Start signal step 1
ST2
BOOLEAN
Start signal step 2
ST3
BOOLEAN
Start signal step 3
ST4
BOOLEAN
Start signal step 4
STFW
BOOLEAN
Forward directional start signal
STRV
BOOLEAN
Reverse directional start signal
2NDHARMD
BOOLEAN
2nd harmonic block signal
6.4.5
Settings
Table 45:
EF4PTOC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
EnaDir
Disable
Enable
-
-
Enable
Enabling the Directional calculation
AngleRCA
-180 - 180
Deg
1
65
Relay characteristic angle (RCA)
polMethod
Voltage
Current
Dual
-
-
Voltage
Type of polarization
UPolMin
1 - 100
%UB
1
1
Minimum voltage level for polarization (UN or
U2) in % of UBase
IPolMin
2 - 100
%IB
1
5
Minimum current level for polarization (IN or I2)
in % of IBase
RPol
0.50 - 1000.00
ohm
0.01
5.00
Real part of source Z to be used for current
polarisation
XPol
0.50 - 3000.00
ohm
0.01
40.00
Imaginary part of source Z to be used for
current polarisation
I>Dir
1 - 100
%IB
1
10
Current level (IN or I2) for direction release in %
of IBase
2ndHarmStab
5 - 100
%
1
20
Second harmonic restrain operation in % of IN
amplitude
Table continues on next page
Section 6
1MRK 511 287-UUS A
Current protection
100
Technical manual
Содержание REC650 ANSI
Страница 1: ...Relion 650 series Bay control REC650 ANSI Technical manual ...
Страница 2: ......
Страница 42: ...36 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 424: ...418 ...
Страница 566: ...560 ...
Страница 636: ...630 ...
Страница 699: ...693 ...