Section 4
Establishing connection and verifying the
IEC 61850 station communication
4.1
Setting the station communication
To enable IEC 61850 station communication:
•
The IEC 61850-8-1 station communication functionality must be on in the
local HMI. Navigate to
Main menu/Configuration/Communication/Station
communication/1:IEC61850-8-1
and set the parameter
Operation
to
On
.
•
To enable GOOSE communication the
Operation
parameter for the
corresponding GOOSE function blocks (GOOSEBINRCV and
GOOSEINTLKRCV) must be set to
On
in the application configuration.
•
To enable GOOSE communication via the front port the parameter
GOOSE
in
Main menu/Configuration/Communication/Station communication/
IEC61850-8-1
must be set to
Front
. To enable GOOSE communication via
rear port the parameter
GOOSE
must be set to
LAN1
.
4.2
Verifying the communication
Connect your PC to the nearby switch and ping the connected IED and the
Substation Master PC, to verify that the communication is working (up to the
transport layer).
The best way to verify the communication up to the application layer is to use a
protocol analyzer, for example, an Ethereal that is connected to the substation bus,
and monitor the communication."
1MRK 511 248-UEN -
Section 4
Establishing connection and verifying the IEC 61850 station communication
29
Commissioning Manual