SuppressMidPos when On suppresses the mid-position during the time tIntermediate of the
connected switches.
The parameter
InterlockCheck decides if interlock check should be done at both select and
operate, Sel & Op phase, or only at operate, Op phase.
12.3.8.3
Switch (SXCBR/SXSWI)
M16675-3 v8
tStartMove is the supervision time for the apparatus to start moving after a command
execution is done from the SCSWI function. When the time has expired, the command
supervision is reset, and a cause-code is given.
During the
tIntermediate time, the position indication is allowed to be in an intermediate (00)
state. When the time has expired, the command supervision is reset, and a cause-code is given.
The indication of the mid-position at SCSWI is suppressed during this time period when the
position changes from open to close or vice-versa if the parameter
SuppressMidPos is set to
On in the SCSWI function.
If the parameter
AdaptivePulse is set to Adaptive the command output pulse resets when a
new correct end position is reached. If the parameter is set to
Not adaptive the command
output pulse remains active until the timer
tOpenPulsetClosePulse has elapsed.
tOpenPulse is the output pulse length for an open command. If AdaptivePulse is set to
Adaptive, it is the maximum length of the output pulse for an open command. The default
length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
tClosePulse is the output pulse length for a close command. If AdaptivePulse is set to
Adaptive, it is the maximum length of the output pulse for an open command. The default
length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
12.3.8.4
Proxy for signals from switching device via GOOSE XLNPROXY
GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1
The
SwitchType setting controls the evaluation of the operating capability. If SwitchType is set
to
Circuit Breaker, the input OPCAP is interpreted as a breaker operating capability, otherwise
it is interpreted as a switch operating capability.
Table 45: Operating capability values for breaker/switches
Value
Breaker operating capability, CbOpCap
Switch operating capability, SwOpCap
1
None
None
2
Open
Open
3
Close – Open
Close
4
Open – Close – Open
Close and Open
5
Close – Open – Close – Open
Larger values handled as 4, both Close and Open
6
Open – Close – Open – Close – Open
7
more
tStartMove is the supervision time for the apparatus to start moving after a command
execution is done from the SCSWI function. When the time has expired, the command
supervision is reset, and a cause-code is given.
During the
tIntermediate time, the position indication is allowed to be in an intermediate (00)
state. When the time has expired, the command supervision is reset, and a cause-code is given.
The indication of the mid-position at SCSWI is suppressed during this time period when the
position changes from open to close or vice-versa if the parameter
SuppressMidPos is set to
On in the SCSWI function.
Section 12
1MRK 505 370-UEN D
Control
298
Busbar protection REB670
Application manual
Содержание REB670 Series
Страница 1: ...Relion 670 SERIES Busbar protection REB670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 64: ...58 ...
Страница 226: ...220 ...
Страница 244: ...238 ...
Страница 358: ...352 ...
Страница 392: ...386 ...
Страница 398: ...392 ...
Страница 436: ...430 ...
Страница 454: ...448 ...
Страница 466: ...460 ...
Страница 474: ...468 ...
Страница 475: ...469 ...