User interface
29
BACnet/IP submenu
When you select the
BACnet/IP
submenu, the
BACnet/IP Settings
page opens. It
provides settings for BACnet/IP.
BACnet/IP Settings page
If your router works as a BACnet/IP router, give the following settings on the
BACnet/IP Settings
page:
Save
button
The
Save
button temporarily saves the changes made on this page.
Note:
You must save your changes before switching to another configuration page.
If you switch to another page without saving, the settings remain unchanged.
Note:
You must activate the configuration before restarting the router module.
Activating the configuration saves all settings permanently. If you restart the router
module without activating the configuration, the old configuration remains active and
the changes are lost.
For activating your settings, see section
BACnet/IP Settings
Description
Network Number
The network number of your local BACnet/IP network. The BACnet
network number must be unique within the entire network.
The network number is valid in the range from 1 to 65.535. The default
value is 1.
UDP Port
The port number for BACnet/IP in your local IP network.
The value is in decimal notation. The default value is 47808 dec.
(0xBAC0 hex.).