![ABB RBIP-01 Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/abb/rbip-01/rbip-01_user-manual_2761019.webp)
Working with the web server
19
Working with the web server
What this chapter contains
This chapter contains instructions on connecting to the web server of the RBIP-01
BACnet/IP Router Module, login/logout instructions, general setting instructions and
a list of the user right levels. For more information on the menu structure of the web
server and detailed setting instructions, see chapter
Connecting to the web server
The router module package contains a crossover network cable. The cable is inside
the package under a lid. Use this cable only for commissioning the router module. It
is not designed to be used for any other purpose after commissioning the module.
You can also use a standard CAT 5 STP cable.
WARNING!
Before installation, switch off the drive power supply. Wait five minutes
to ensure that the capacitor bank of the drive is discharged. Switch off all dangerous
voltages connected from external control circuits to the inputs and outputs of the
drive.
Note
: Do not connect the router module to the network before you have
commissioned the device!
For more information, see chapter
1. Connect the crossover network cable to the RJ-45 connector of the router
module with the network connector of your PC. Avoid parallel runs with power
cables, for example, motor cables.
2. Switch the drive power on.
3. Wait till the steady orange STATUS LED of the router module is no more on. It is
lit for approximately 25 seconds in the starting phase after power-up. During
start-up, the router module does not respond. The flashing orange STATUS LED
after start-up indicates that the module is running with factory settings and needs
to be commissioned.
4. If not done, set your PC to run as a Dynamic Host Configuration Protocol
(DHCP) client or set the IP address of your PC manually to 192.168.0.2/
255.255.255.0.
• If you use DHCP, activate the DHCP server in the router module by pressing
and holding the Reset switch of the router module down for more than 5
seconds, but not longer than 10 seconds. As soon as the STATUS LED flashes
red and green alternating, the DHCP server is active.