Technical data and types: PVS980-CS
Type code (PVS980-CS-...
Data
4600
4400
4200
4000
2300
2200
2100
2000
4600
4440
4200
4000
2300
2200
2100
2000
Maximum rating in kVA
Inverter
PVS980
Inverter
1500 V
Maximum operating DC input
voltage
2
2
2
2
1
1
1
1
Number of inverters
2
2
2
2
1
1
1
1
Number of independent mppt
978-
1500
935-
1500
893-
1500
850-
1500
978-
1500
935-
1500
893-
1500
850-
1500
mppt range @ 35 °C in V
978-
1100
935-
1100
893-
1100
850-
1100
978-
1100
935-
1100
893-
1100
850-
1100
mppt range @ 50 °C in V
690 V
660 V
630 V
600 V
690 V
660 V
630 V
600 V
AC output voltage
MV transformer
Oil immersed (ONAN)
Transformer type
4600
4440
4200
4000
2300
2200
2100
2000
AC power at 35 °C in kVA
4182
4000
3818
3636
2091
2000
1909
1818
AC power at 50 °C in kVA
2
2
2
2
1
1
1
1
Number of secondary windings
690 V
660 V
630 V
600 V
690 V
660 V
630 V
600 V
Low voltage level
≤ 36 kV
Medium voltage level range
50 Hz or 60 Hz
Rated frequency
Mineral (vegetable optional)
Oil type
± 2 x 2.5%
Tap changer
AI / AI
Winding material
(primary / secondary)
Yes
Eco efficiency optional
MV switchgear
ABB SafePlus (SF
6
-insulated)
Switchgear type
630 A
Rated current
Single (CV) or double feeder (CCV)
Configuration
Circuit breaker (16 kA or 20 kA / 20 kA or 25 kA)
Protection
(up to 24 kV / 36 kV)
ABB REJ603 (others on request)
Protection relay type
Yes
Motorized optional
Auxiliary supply
10 kVA (20 kVA, 39 kVA optional)
Auxiliary transformer power
690 V
660 V
630 V
600 V
690 V
660 V
630 V
600 V
Auxiliary transformer primary
voltage level
400-230 V
Auxiliary transformer second-
ary voltage level
Yes
Low voltage distribution panel
for auxiliary functions
Mechanical characteristics
64 Technical data