44 Planning the electrical installation
Inverters without input DC fuses (0F291)
If the standard input DC fuses are not suitable for the customer application, the inverter
can be delivered without input DC fuses (0F291). In this case, install appropriate
DC fuses to protect the inverter DC circuit and the DC input cables in a short-circuit
situation. Protect the positive and negative poles of an input with separate fuses. The
power loss of a fuse may never exceed 25 W.
For the recommended DC input fuse options, refer to
page
.