80 Planning the electrical installation
Supplying power for the auxiliary circuits
Supply the inverter with rated auxiliary voltage. Protect the supply according to local
regulations with, eg, fuses and/or fault current breakers. Do not connect any additional
appliances to the inverter without consulting with ABB.
Implementing the low voltage ride-through function
The user can define by parameters when the inverter must stay connected to the grid (ie,
the depth and length of the grid voltage transient). The user can also define how much the
inverter supports the grid with capacitive reactive current during the grid voltage transient.
For more information, see
PVS800 central inverters firmware manual
(3AUA0000058422
[English]).
If a low voltage ride-through function is used with the PVS800-57-100kW-A, PVS800-57-
250kW-A or PVS800-57-315kW-B inverters, the auxiliary power supply must be
uninterruptible (that is, the auxiliary voltage is not allowed to have voltage dips). Use of an
external UPS device (uninterruptible power supply) is recommended in that case.
Supplying circuits from the AC output of the inverter
If the AC output of the inverter is used for supplying any circuits, provide galvanic isolation
as shown in the diagram below. A denotes other equipment and B supplying auxiliary
circuit of the inverter. See also
Connecting the external power supply cable for the
. For instructions on selecting the transformer, see section
on page
.
PVS800-57
A
High voltage / Low voltage
PVS800-57
Q10
B
L N PE
High voltage / Low voltage
Содержание PVS800-57-0100kW-A
Страница 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Страница 4: ......
Страница 22: ...20 Safety instructions ...
Страница 64: ...62 Operation principle and hardware description ...
Страница 74: ...72 Mechanical installation ...
Страница 90: ...88 Electrical installation PE PE PE ...
Страница 124: ...122 Maintenance ...
Страница 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Страница 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Страница 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Страница 155: ...Dimension drawings 153 Frame R8i R8i 2 DC inputs option 2H382 or 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Страница 158: ...156 Dimension drawings R8i DC terminals of units with 2 DC inputs option 2H382 3AXD50000016935 ...
Страница 159: ...Dimension drawings 157 R8i DC terminals of units with 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 160: ...158 Dimension drawings R8i DC terminals of units with 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 162: ...160 Dimension drawings Frame 2 R8i 2 R8i 4 DC inputs option 4H382 or 5 DC inputs option 5H382 3AXD50000015007 ...
Страница 163: ...Dimension drawings 161 2 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015007 ...
Страница 164: ...162 Dimension drawings 2 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015007 ...
Страница 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Страница 170: ...168 Dimension drawings Frame 3 R8i 3 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015006 ...
Страница 171: ...Dimension drawings 169 3 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015006 ...
Страница 172: ...170 Dimension drawings 3 R8i 16 DC inputs option 16H382 or 20 DC inputs option 20H382 3AXD50000015006 ...
Страница 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Страница 178: ...176 Dimension drawings ...
Страница 179: ...Further information More information about ABB products for solar applications on the Internet www abb com solar ...
Страница 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...