42 Operation principle and hardware description
Positive or negative pole grounding (oF282 and
+F283)
The positive and negative pole grounding options can be used when solar modules require
grounding of inverter DC poles. The grounding of the poles complies with standard
IEC 62109-2. One DC line needs to be grounded for certain thin-film photovoltaic module
types and if required by country-specific regulations.
The grounding is always connected when auxiliary power is connected, except when the
automatic photovoltaic generator insulation check is done before the inverter starts.
The grounding wire is protected by a fuse on the PGND-02 board. Due to personnel
protection reasons, the grounding is disconnected when sudden level changes are
monitored from the grounding wire current.
The grounding resistance can be adjusted by the user. For instructions, see page
Reduced run operation in case of a hardware failure
If an inverter module or an LCL filter is out of order, it is possible to continue running the
inverter with reduced output current. In this case the inverter controls only modules which
are unbroken. Inverter output current is reduced in relation to the removed modules. For
example, if one inverter module is broken in PVS800-57-1000kW-C, the inverter output
current is reduced to 66.7% of the nominal current. Reduced run is not possible with
inverters that have only one inverter module.
To operate the PVS800 with reduced run, you must remove the charging circuit fuses
specified in the tables below. However, you do not have to remove the broken inverter
module or LCL filter. This is possible because broken parts can be isolated with AC and
DC contactors inside the PVS800 cabinet. For removing the broken component, obey the
instructions in chapter
Inverter modules are divided into two control groups, which can be enabled or disabled
according to the need. If a module group is disabled, the inverter modules which are part
of that group are not used. The following tables list the possible control combinations in the
reduced run operation.
PVS800-57-500kW-A and PVS800-57-630kW-B:
PVS800-57-875kW-B and PVS800-57-1000kW-C:
Inverter control unit parameter
16.05 USED MODULES
Description
Reduced
output
current
Charging circuit
fuses to be
removed
GROUP 1
Left inverter module (U1) is used.
50%
F20.3-4
GROUP 2
Right inverter module (U2) is
used.
50%
F20.1-2
GROUPS 1 and 2 (default)
Left (U1) and right (U2) inverter
modules are used.
100%
None
Inverter control unit parameter
16.05 USED MODULES
Description
Reduced
output
current
Charging circuit
fuses to be
removed
GROUP 1
Left inverter module (U1) is used.
33.3%
F20.3-6
Содержание PVS800-57-0100kW-A
Страница 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Страница 4: ......
Страница 22: ...20 Safety instructions ...
Страница 64: ...62 Operation principle and hardware description ...
Страница 74: ...72 Mechanical installation ...
Страница 90: ...88 Electrical installation PE PE PE ...
Страница 124: ...122 Maintenance ...
Страница 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Страница 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Страница 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Страница 155: ...Dimension drawings 153 Frame R8i R8i 2 DC inputs option 2H382 or 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Страница 158: ...156 Dimension drawings R8i DC terminals of units with 2 DC inputs option 2H382 3AXD50000016935 ...
Страница 159: ...Dimension drawings 157 R8i DC terminals of units with 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 160: ...158 Dimension drawings R8i DC terminals of units with 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 162: ...160 Dimension drawings Frame 2 R8i 2 R8i 4 DC inputs option 4H382 or 5 DC inputs option 5H382 3AXD50000015007 ...
Страница 163: ...Dimension drawings 161 2 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015007 ...
Страница 164: ...162 Dimension drawings 2 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015007 ...
Страница 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Страница 170: ...168 Dimension drawings Frame 3 R8i 3 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015006 ...
Страница 171: ...Dimension drawings 169 3 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015006 ...
Страница 172: ...170 Dimension drawings 3 R8i 16 DC inputs option 16H382 or 20 DC inputs option 20H382 3AXD50000015006 ...
Страница 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Страница 178: ...176 Dimension drawings ...
Страница 179: ...Further information More information about ABB products for solar applications on the Internet www abb com solar ...
Страница 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...