14 Safety instructions
Electrical safety
These warnings are for all personnel who do work on the inverter, its input and output
cables, the transformer or photovoltaic generator.
WARNING!
Obey these instructions. If you ignore them, injury or death, or
damage to the equipment can occur.
•
If you are not a qualified electrician, do not do electrical installation or
maintenance work.
•
Never work on the photovoltaic generator or the inverter or its input or output cables
when the inverter is connected to electrical power system or to the photovoltaic
generator. After disconnecting the inverter from the electrical power system and the
DC input, always wait for 5 min to let the intermediate circuit capacitors discharge
before you start working on the inverter, its input and output cables or the photovoltaic
generator.
Always ensure by measuring with a multimeter (impedance at least 1 Mohm) that:
1)
Voltage between inverter phases (L1, L2, L3) and the frame is close to 0 V.
2)
Voltage between the inverter module terminals (UDC+ and UDC-) and inverter DC
input terminals (L+ and L-) and the frame is close to 0 V.
•
Before working inside the inverter cabinet, isolate the AC line cables and busbars from
the electrical power system with the disconnector of the power system transformer.
Also, isolate the inverter from the photovoltaic generator with the safety switch of the
generator or by other means. The grid disconnecting device (disconnecting means) of
the inverter does not isolate the AC output cables and terminals from the electrical
power system. The DC main switch/switches or DC input circuit breakers do not
isolate the DC input cables or terminals from the DC voltage supplied by the
photovoltaic generator.
•
Before working inside the inverter cabinet, switch off or isolate the auxiliary voltage
supply from the inverter.
•
Before working on the unit, apply temporary grounding for work. See page
•
Do not work on the control cables when power is applied to the inverter or to the
external control circuits. Externally supplied control circuits may cause dangerous
voltages inside the inverter even when the main power on the inverter is switched off.
•
Live parts inside the cubicle are protected against direct contact when all protective
plastic covers and metallic shrouds are in place. Pay special attention when handling
sharp metallic shrouds.
•
Do not make any insulation or voltage withstand tests on the inverter or inverter
modules.
Note:
•
The DC connection terminals (UDC+, UDC-, L+ and L-) carry a dangerous DC voltage
(up to 1100 V).
•
External wiring can supply dangerous voltages to the terminals of relay outputs (RO1,
RO2 and RO3).
•
Depending on the external and internal wiring, dangerous voltages (115 V or 230 V)
may be present at different terminals in the auxiliary connection unit.
•
With oF282 and +F283, one of the poles of the photovoltaic generator is
grounded, and therefore, the other pole has full voltage against ground (up to 1100 V).
Содержание PVS800-57-0100kW-A
Страница 1: ...ABB solar inverters Hardware manual PVS800 57 central inverters 100 to 1000 kW ...
Страница 4: ......
Страница 22: ...20 Safety instructions ...
Страница 64: ...62 Operation principle and hardware description ...
Страница 74: ...72 Mechanical installation ...
Страница 90: ...88 Electrical installation PE PE PE ...
Страница 124: ...122 Maintenance ...
Страница 152: ...150 Dimension drawings Frame R7i 3AUA0000083128 ...
Страница 153: ...Dimension drawings 151 AC output 3AUA0000083128 ...
Страница 154: ...152 Dimension drawings 3AUA0000083128 One DC input Four DC inputs ...
Страница 155: ...Dimension drawings 153 Frame R8i R8i 2 DC inputs option 2H382 or 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 156: ...154 Dimension drawings R8i 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 157: ...Dimension drawings 155 R8i AC output terminals 3AXD50000016935 ...
Страница 158: ...156 Dimension drawings R8i DC terminals of units with 2 DC inputs option 2H382 3AXD50000016935 ...
Страница 159: ...Dimension drawings 157 R8i DC terminals of units with 4 DC inputs option 4H382 3AXD50000016935 ...
Страница 160: ...158 Dimension drawings R8i DC terminals of units with 8 DC inputs option 8H382 3AXD50000016935 ...
Страница 162: ...160 Dimension drawings Frame 2 R8i 2 R8i 4 DC inputs option 4H382 or 5 DC inputs option 5H382 3AXD50000015007 ...
Страница 163: ...Dimension drawings 161 2 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015007 ...
Страница 164: ...162 Dimension drawings 2 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015007 ...
Страница 165: ...Dimension drawings 163 2 R8i AC output terminals 3AXD50000015007 ...
Страница 170: ...168 Dimension drawings Frame 3 R8i 3 R8i 8 DC inputs option 8H382 or 10 DC inputs option 10H382 3AXD50000015006 ...
Страница 171: ...Dimension drawings 169 3 R8i 12 DC inputs option 12H382 or 15 DC inputs option 15H382 3AXD50000015006 ...
Страница 172: ...170 Dimension drawings 3 R8i 16 DC inputs option 16H382 or 20 DC inputs option 20H382 3AXD50000015006 ...
Страница 173: ...Dimension drawings 171 3 R8i AC input terminals 3AXD50000015006 ...
Страница 178: ...176 Dimension drawings ...
Страница 179: ...Further information More information about ABB products for solar applications on the Internet www abb com solar ...
Страница 180: ...Contact us www abb com solar 3AUA0000053689 Rev H EN EFFECTIVE 2014 07 09 ...