8 - Maintenance
R
eplacing fan section (internal)
Some inverter parts may be subject to voltages that could be hazardous for the operator.
Before performing any work on the inverter, refer to “Inverter total de-energization and
safe access” chapter on this manual to know all the necessary step to safely operate
on the inverter.
Procedure for replacing one of the two fan sections:
1.
Perform the “Inverter total de-energization and safe access” procedure
before operate on the inverter.
2.
Open the front wiring box cover
07
.
3.
Remove the 2 screws (STEP A).
4.
Pull out the fan section (STEP B).
5.
Place the new fan section in the reverse way of previous steps
B