5 - Installation
I
ndependent channel configuration (default configuration)
This configuration involves the use of the two input channels (MPPT)
in independent mode. This means that the jumpers between the two
channels (positive and negative) of the DC input terminal block
14
must not be installed and the switch
16
located on the main board
must be set to “IND”.
P
arallel channel configuration
This configuration uses the two input channels (MPPT) connected in
parallel. This means that the jumpers between the two channels (posi-
tive and negative) of the DC input terminal block
14
must be installed
and the switch
16
located on the main board must be set to “PAR”.
16
14
16