![ABB PRO-33.0-TL Series Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/abb/pro-33-0-tl-series/pro-33-0-tl-series_service-manual_3045376057.webp)
Parameters 57
No.
Name/Value/Range
Description
Default
FbEq (16b/32b)
132 Autoreset
132.01
Autoreset counter
Shows the number of autoresets. Can be cleared
to allow better monitoring.
0
-
1 = 1
132.02
Autoreset boot counter
Counts the number of forced reboots. Some faults
can be reset / cleared only with a firmware reboot.
The counter increments when the Autoreset
function orders a reboot.
0
-
- / 1 = 1
132.03
Overcurrent trials
Sets the number of overcurrent autoreset trials.
5
0 … 20
1 = 1
132.04
Overcurrent reset delay
Sets the delay for overcurrent autoreset.
10 s
1 … 3000 s
1 = 1 s
132.05
DC protection trials
Number of DC protection autoreset trials.
3
0 … 20
1 = 1
132.06
DC protection reset delay
Sets the delay for DC protection autoreset.
10 s
1 … 3000 s
1 = 1 s
132.07
Ground impedance trials
Sets the number of ground impedance autoreset
trials.
50
0 … 100
1 = 1
132.08
Ground impedance reset
delay
Sets the delay for ground impedance autoreset.
900 s
1 … 7200 s
1 = 1 s
132.09
Ground current trials
Sets the number of ground current autoreset
trials.
-
0 … 100
1 = 1
132.10
Ground current reset delay Sets the delay for ground current autoreset.
-
1 … 7200 s
1 = 1 s
Содержание PRO-33.0-TL Series
Страница 1: ...ABB solar inverters Service menu guide PRO 33 0 TL string inverters ...
Страница 4: ......
Страница 8: ...8 ...
Страница 12: ...12 Service menu ...
Страница 36: ...36 Program features ...
Страница 100: ...100 Parameters ...
Страница 112: ...112 Tools ...
Страница 121: ......
Страница 122: ...www abb com solarinverters Contact us 3AXD50000015823 Rev C EN 2017 06 29 ...