Startup guide for Pluto Safety PLC, connected in a bus system

1. Check the bus cable

·

  How many meters of bus cable have been

used?

·

  Is the system connected with stub

cables?

·

  How long is each stub?

·

 

What is the total length of stub cables?

·

  Resistors for end termination must only

be connected in the beginning and the
end of the system.

·

  When  measuring the resistance between

CH and CL at one Pluto (all units shall be
dead) the resistance shall be somewhat
under 60 

Ω

.

The following data are necessary to select the correct communication speed in the system. A lower speed
gives the possibility to communicate over a longer distance, but it results in that somewhat fewer Pluto’s can
be connected. A more detailed description can be found in the Pluto Hardware Manual, chapter Bus
communication.

Bus speed

Cable length

Stub length

Total stub length

100 kbit/s

600 m

25 m

120 m

125 kbit/s

500 m

20 m

100 m

200 kbit/s

300 m

13 m

70 m

250 kbit/s

250 m

10 m

50 m

400 kbit/s

150 m

6 m

30 m

500 kbit/s

100 m

5 m

25 m

800 kbit/s

60 m

3 m

15 m

1 Mbit/s

< 20 m

1 m

5 m

Communication speed for the project is set in the Pluto Manager. Open the window Project NoName, open
the pop-up menu under Baudrate Pluto Canbus and select the correct speed.

2. Read the IDFIX number

·

 

Must be performed before the program is downloaded to any of the units.

·

 

The programming cable must be connected to each Pluto when reading that particular Pluto’s IDFIX.

·

 

Read IDFIX numbers to all Pluto’s using the command “Copy online IDFIX to clipboard” under the
menu “Tools”. Paste the number to the corresponding Pluto.