MEDIUM VOLTAGE PRODUCTS
OVR
–
Three phase mechanically ganged reclosers
Operator’s
quick reference guide for OVR-15, OVR-27 & OVR-38
Product related Safety Notices
The OVR three phase reclosers should be installed within the design limitations as
described on the nameplate and the instructions mentioned in instruction and
maintenance manual. In addition, always follow your
company’s
safety procedures.
For the safety of the personnel performing maintenance operations on the recloser
or connecting equipment, all components should be electrically disconnected by
means of a visible break and securely grounded.
For detailed information, please refer the instruction manual provided with the
equipment or contact ABB representative.
Copy Right
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
Disclaimer
This document is to be read along with the instruction manual of the product.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this document or application of the equipment.
A.
Powering-up the recloser
It is assumed that the recloser is already installed as per instructions provided in instruction manual. Ensure the cabinet is properly grounded,
that all MCBs are OFF (lower down) and that the service selector switch is in DISCHARGE position.
1.
Open the front, upper & lower auxiliary doors of LV cabinet.