2TLC
172289M0201
Rev C
21
www.abb.com/jokabsafety
2018-04-17
5 Electrical connections
All electrical connections to the active unit are made through a male M12-8 pole connector located on the lower part of
the active unit.
5.1 Active unit
Pin
Wire
1
Function
Connection to
Refer to
1
White
2
RESET/
ACKNOWLEDGE/
RESET MODE
Auto. Reset with no function
+24 VDC
Auto. Reset with Acknowledge
function or Alignment mode
NC contact to +24 VDC
Manual Reset
NC contact to 0 V
2
Brown
Supply
+24 VDC
3
Green
2
EDM SELECTION
Activate EDM
Not connected or 0 V
Deactivate EDM
+24 VDC
4
Yellow
EDM
Function used/activated
NC contact of force-guided
relay
Function not used/deactivated
Not connected or 0 V
5
Grey
OSSD1
Safety control module for ex.
6
Pink
OSSD2
Safety control module for ex.
7
Blue
Supply
0 V
8
Red
Earth
Earth
1
Colors according to ABB Jokab Safety standard cables.
2
The “RESET/ACKNOWLEDGE/RESET MODE” wire, the “EDM SELECTION” wire and the supply wires MUST be connected in order
for the device to function. The other wires may be floating.