Troubleshooting flowchart
Problem starng or connecng
the Flexpendant
Check connecon
from A2.X8 to HMI
extension cable
Connecon
not OK
Repair connecon
Check connecon
from HMI extension cable
to Flexpendant
Connecon OK
Connecon OK
Connecon
not OK
Repair connecon
Start Flexpendant
OK
Problem solved
Replace Flexpendant
Not starng
xx2100001556
Detailed working procedure
Note
Action
See
Operating manual - OmniCore
.
Try resetting the FlexPendant using the reset
button located next to the USB port.
1
If it is not connected, repair the
connection and go to step six.
Check that the extension cable is correctly con-
nected to the controller through the HMI signal
connector.
2
Check the pins in the connector.
If it is ok, go to the next step.
Continues on next page
178
Product manual - OmniCore E10
3HAC079399-001 Revision: C
© Copyright 2019-2022 ABB. All rights reserved.
6 Troubleshooting
6.2.5 Problem starting or connecting the FlexPendant
Continued