IB 6.1.2.8-1B 

      

INSTRUCTIONS FOR MPS-C 2000 

ELECTRONIC TRIP CONTROL UNIT 

 

ABB 

Courtesy of NationalSwitchgear.com

Содержание MPS-C 2000

Страница 1: ...IB 6 1 2 8 1B INSTRUCTIONS FOR MPS C 2000 ELECTRONIC TRIP CONTROL UNIT ABB Courtesy of NationalSwitchgear com ...

Страница 2: ...the matter should be referred to the nearest Sales Representative CONTENTS PAGE INTRODUCTION 3 FUNCTIONS 4 SETTINGS 4 RANGE SELECTION 4 LONG TIME FUNCTION 4 SHORT TIME FUNCTION 4 INSTANTANEOUS FUNCTION 5 GROUND FUNCTION 5 CURRENT UNBALANCE 6 CURRENT SENSOR THRESHOLDS 6 INFORMATION FUNCTION 6 TEST FUNCTIONS 7 VOLTAGE INTERFACE MODULE VIM 7 SETTINGS 7 MPS C 2000 SETUP INSTRUCTIONS 8 GENERAL INSTRUCT...

Страница 3: ...to an accuracy of within 1 of the cicuit breaker rating The Voltage Interface Module VIM option measures voltage to an accuracy of within 1 of the circuit breaker rating and power to within 2 of the circuit breaker rating The trip unit is completely self powered taking the the tripping energy from the current through the breaker without any auxiliary power supply The complete control of the circui...

Страница 4: ...des the primary amperage used as the base for the unit It is either set for the 1 X or 0 5 X the breaker rating Default is 1 X 2 2 Long Time Function 2 2 1 Threshold pickup settings The range of settings is 0 5 to 1 0 in steps of 0 1 Multipliers are used in conjunction with sensor rating and the range selector Multipliers are selected by keypad input and displayed on the LCD Default is 1 0 2 2 2 T...

Страница 5: ... 9 10 11 12 DISABLED The settings are multiples of the range selector setting and are made via the keypad and the LCD screen If the short time unit is disabled the instantaneous unit cannot be disabled Default is 12 2 4 2 Trip time There is no intentional delay in the instantaneous function 2 4 3 The instantaneous unit includes a jumper on the circuit board which eliminates the possibility of inst...

Страница 6: ...ground element 2 6 Current Unbalance 2 6 1 Pickup settings 5 to 50 in increments of 1 and DISABLED These changes can be made either via the keypad and LCD or the NIM communications unit Default is DISABLED The current unbalance function is only available for systems with VIM attached 2 7 Current Sensor Thresholds 2 7 1 Long time 0 5X to 1 0X of sensor rating in increments of 0 1 Short time 2X to 1...

Страница 7: ...factor and frequency processing based on current data from the MPS C 2000 box c Performs calculations to determine voltage unbalance and undervoltage faults 4 2 If a VIM device is installed the MPS C 2000 unit must be connected to a NIM communications unit 4 3 If a VIM is installed in the unit a cable connects the unit to the potential transformer located on the rear of the MPS C 2000 mounting pla...

Страница 8: ...setup screen Subsequent Main Menu screens are accessed by pressing the E key and the up and down keys See section 6 5 1 3 Each Main Menu has a Submenu used for entering and displaying values These are accessed by pressing the E key while in the Main Menu The up and down keys are used in the submenus to display the desired type of values or settings and the E key is pressed again to access these Th...

Страница 9: ... MAIN MENU Metering Menu MAIN MENU Show Settings MAIN MENU Change Settings MAIN MENU Records Menu INITIAL SCREEN Press E or wait 3 seconds Press E Press Up and Down Arrows METER MENU Load Values Press E SETTINGS MENU MPS Settings Press E CHANGE MENU MPS Settings Press E RECORDS MENU MPS Fault Event Press E SUBMENUS See sec 6 2 See sec 6 3 See sec 6 4 See sec 6 5 This screen is displayed when unit ...

Страница 10: ...ached METER MENU Demand Values Press Up and Down Arrows DEMAND VALUES Ia Press E Ib Ic In KW3p KVAr3p KWHr3p KVarHr3p These values will not be displayed if a VIM is not attached Press C Press C 6 2 METERING SUBMENU E E KEYPAD INPUT SEQUENCE FOR METERING SUBMENU E Ia Ib Ic In C E LOAD VALUES Ia DEMAND VALUES Ia METER MENU Demand Values Default screen display Press keys in this sequence to access me...

Страница 11: ...SWORD Scroll up and down using arrow keys SETTINGS MENU VIM Settings Press Up and Down Arrows SHOW VIM SET V Unbal Press E V Unb Dly UV Pkup UV Delay Dmnd Intvl Press C Press C 6 3 SETTINGS SUBMENU E KEYPAD INPUT SEQUENCE FOR SETTINGS SUBMENU E Ia Ib Ic In C E SHOW SETTINGS Rating SHOW VIM SET V Unbal Default screen display Press keys in this sequence to access Settings submenus E Courtesy of Nati...

Страница 12: ... In C E CHANGE SETTINGS Rating Press E PRESS E TO CHANGE SETTINGS Press C ENTER PASSWORD CHNG VIM SET V Unbal Press E Press C PRESS E TO CHANGE SETTINGS E E 6 4 1 To change settings PRESS E an asterisk will appear after the setting TOGGLE BETWEEN SETTINGS USING LEFT AND RIGHT ARROW KEYS PRESS E TO ACCEPT THEN PRESS C See instructions below for changing settings sec 6 4 1 Press keys in this sequenc...

Страница 13: ...0 Volts in increments of 1 volt UNDERVOLTAGE DELAY 10 to 25 0 seconds in increments of 1 and DISABLED DEMAND INTERVAL 15 30 and 60 minutes 6 4 3 Password Protection If a password has not been programmed into the unit the PASSWORD screen can be bypassed simply by pressing E To enter a password scroll down to the PASSWORD screen in the CHANGE SETTINGS Submenu press E using the UP and DOWN keys scrol...

Страница 14: ...ENU Breaker Oper BREAKER OPER Count Press E KSIa KSIb KSIc Press C Press C 6 5 RECORDS SUBMENU KEYPAD INPUT SEQUENCE FOR RECORDS SUBMENU E Ia Ib Ic In C E RECORDS MENU VIM Fault Event VIM FAULT EVENT Type Vab Vbc Vca Press E Press C E E C E Press Up and Down Arrows MPS FLT EVENT Event BREAKER OPER Count VIM FAULT EVENT Type Courtesy of NationalSwitchgear com ...

Страница 15: ...IB 6 1 2 8 1B Page 15 ABB Notes Courtesy of NationalSwitchgear com ...

Страница 16: ...IB 6 1 2 8 1B Page 16 ABB Notes Courtesy of NationalSwitchgear com ...

Страница 17: ...IB 6 1 2 8 1B Page 17 ABB Notes Courtesy of NationalSwitchgear com ...

Страница 18: ...IB 6 1 2 8 1B Page 18 ABB ABB Inc 2300 Mechanicsville Road Florence SC 29501 Phone 843 413 4700 Fax 843 413 4850 ABB Courtesy of NationalSwitchgear com ...