10
10
M1M 30
POWER METER USER MANUAL
3.5.Technical data
Auxiliary power supply
Voltage
100-230 V AC/DC ±15%
Frequency
50 - 60Hz ±5%
Power consumption
5VA max
Installation category
CAT III 300V class per IEC 61010-1 edition 3
Protection fuse
T1 A-277 VAC
Measurement accuracy
IEC 61557-12
IEC 61557-12 PMD/S/K55/1 (M1M 30 Modbus, M1M 30 Ethernet)
IEC 61557-12 PMD/S/K55/0.5 (M1M 30 I/O)
Active energy
IEC 61557-12 Class 1 (M1M 30 Modbus, M1M 30 Ethernet)
IEC 61557-12 Class 0.5 (M1M 30 I/O)
IEC 62053-22 Class 0.5S (M1M 30 I/O)
Reactive energy
IEC 61557-12 Class 2
Active power
IEC 61557-12 Class 1 (M1M 30 Modbus, M1M 30 Ethernet)
IEC 61557-12 Class 0.5 (M1M 30 I/O)
Reactive power
IEC 61557-12 Class 2
Apparent power
IEC 61557-12 Class 2
Voltage
IEC 61557-12 Class 0.5
Current
IEC 61557-12 Class 0.5
Neutral Current (calculated)
IEC 61557-12 Class 1
Frequency
IEC 61557-12 Class 0.1
Unbalance
IEC 61557-12 Class 0.5
Harmonics, THD (Current, voltage)
IEC 61557-12 Class 1
Voltage Measurement inputs
Voltage Range
80-265 VAC(L-N)
Type
Single-phase, three-phase (3P, 3P+N)
Rated frequency
50Hz or 60Hz
Protection fuse
T1 A-277 VAC
Current measurement inputs
Current input mode
Indirect insertion with CT
Rated current at secondary side of CT
1A or 5A
Range without accuracy derating
50mA-6A
I/O
Digital Output
Number of output channels
2
Voltage
5-48VDC
Current
2-100mA
Digital Input
Number of input channels
2 (M1M 30 I/O only)
Voltage
24VDC
Mechanical properties
Overall Dimensions
96 mm x 96 mm x 85 mm
IP degree of protection (IEC 60529)
Front: IP51
Terminals: IP20
Max. weight
345g
Содержание M1M 30 Series
Страница 1: ...M1M 30 User manual 2CSG445091D0201 Power meter M1M 30 User manual ...
Страница 2: ......
Страница 12: ...12 92 0 0 8 mm 92 0 0 8 mm IEC 61554 M1M 30 POWER METER USER MANUAL 4 Installation 4 1 Assembly 1 3 2 ...
Страница 13: ...13 92 0 0 8 mm 92 0 0 8 mm IEC 61554 M1M 30 POWER METER USER MANUAL 4 2 Disassembly 2 1 ...
Страница 58: ... ...
Страница 59: ......