A ppENDIX B
Modbus registers
NOTICE
The map register offset in this Appendix is Base 0 (first register address is at 0).
Holding registers
The Holding registers consist of 16 bits. They can be read and written. The address (1 byte) is sent
before each command. A CRC (2 bytes) is sent after each command.
Register name
Register
address
Data type
Value range
Default
value
Description
address
200
USIGN8
1 – 247
247
also known as Slave ID
Baud rate
201
TABENUM8
1 = 1200
2 = 2400
3 = 4800
4 = 9600
5 = 19200
4 = 9600
this is the baudrate used during Modbus
communication
parity
202
TABENUM8
0 = None
1 = Even
2 = Odd
0
this is the parity bit in the Modbus frame
Stop bit
203
TABENUM8
1 = One stop bit
2 = two stop bits
1
this is the number of stop bits in the
Modbus frame
Map Register
Offset
204
TABENUM8
0 = 0
1 = 1
1
this offset is added from the address
received in the Modbus frame message.
Defines the register base number
Delay time
206
USIGN8
1 – 200ms
50 ms
Define the period of time before the LWt
sends out a response
Swap Mode
3000
TABENUM8
0 = aBCD,
1 = CDaB,
2 = DCBa,
3 = BaDC
1 = CDaB
Define the byte order for the Floating
point Format Code register
Содержание LWT300 series
Страница 1: ... USER GUIDE LWT300 series Guided wave radar level transmitter Modbus ...
Страница 36: ...Page intentionally left blank ...
Страница 40: ...Page intentionally left blank ...
Страница 66: ...Page intentionally left blank ...
Страница 70: ...Page intentionally left blank ...
Страница 76: ...Page intentionally left blank ...
Страница 96: ...Page intentionally left blank ...
Страница 98: ...Page intentionally left blank ...
Страница 104: ...Page intentionally left blank ...
Страница 105: ...Page intentionally left blank ...
Страница 106: ...Page intentionally left blank ...
Страница 107: ......