OI-LLT100-EN Rev. D |
User Guide
29
10 Configuring process alarms
Figure 20
Limits variables diagram
By design, when a monitored process is within defined limits,
the LLT100 analog signal output is between 4 mA and 20 mA.
If the instrument detects a failure, the analog signal is driven
higher or lower.
The
Process Alarm
menu allows you to configure saturation
and failure alarms when the process variable (PV) goes outside
these limits.
10.1 Setting failure mode
The LLT100 allows you to set which alarm value will trigger the
failure mode (see “Setting measurement value high and low
limits” on page 19). Generally, the High value will trigger
this mode.
To set which alarm will trigger the failure mode:
1. From the
Process Alarm
menu, select
Failure Mode.
2. From the
Failure Mode
screen, select
High
or
Low
to
determine which alarm will trigger the failure mode.
3. Press
OK
.
10.2 Defining alarm delays
A delay was implemented to prevent raising alarms too quickly
after the threshold has been reached.
To set an alarm delay:
1. From the
Process Alarm
menu, select
Alarm Delay.
2. From the
Alarm Delay
screen, edit the length of time during
which an alarm can persist before the alarm is actually
raised.
3. Press
OK
.
Vessel height
Ullage
Level
High High Alarm
High Alarm
Low Low Alarm
Low Alarm
Содержание LLT100
Страница 8: ...This page intentionally left blank ...
Страница 10: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank ...
Страница 22: ...This page intentionally left blank ...
Страница 26: ...This page intentionally left blank ...
Страница 44: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 66: ...This page intentionally left blank ...
Страница 67: ......