LevelMaster 7100 User manual 2105835 Rev AA
| 87
Command
syntax
Description
U**T
Measure displacement in new test mode
U**ED
EEPROM dump in DEC 16x16 format
U**EE
EEPROM dump in DEC 8x32 format
U**EH
EEPROM dump in HEX 8x32 format
U**ERaaaE
Wddd
Write to memory aaa data to ddd
U**F
Read/write mode number
U**N
Read/write unit number
U**OL
Oil level offset
U**OW
Water level offset
U**OF
Temperature reading offset
U**OV
Voltage reading offset
U**PS
Phase shift test
U**V
Return software version
U**S
Return settings
UxxPxxxxxx
Enter password
UxxCxxxxxx
Change password
U**GS
Gain set
U**GR
Gain read
U**GAxxx
Gain all set
A.2
Activating the tank level pass-through
To use terminal mode for tank level pass-through:
1.
Connect the PC running PCCU32 to the flow computer with either an MMI cable (RS-232), a USB cable or an Ethernet
cable.
2. Start
PCCU.
3. Click
Entry
on the toolbar.
4. Click
Communications
on the navigation tree.
5. Set the
Unkey Delay to
1.
6. Click
Send
.
7. Click
Terminal
on the toolbar.
8.
To activate Tank Level Pass Through:
a. Type
“
TLPT
=
1”
(
T
ank
L
evel
P
ass
T
hrough Activate), at the prompt -> for XSeries FCUs and XRCs.
b. Type
“
TLPT=0”
(
T
ank
L
evel
P
ass
T
hrough Activate), at the prompt -> for 64XX and 67XX FCUs.
9.
Wait for the prompt LM> to appear to issue commands. The prompt indicates that the LevelMaster protocol is now in use.
a.
For LevelMasters with boards whose firmware version is 5.015-5.018, use the commands listed in Table 12.
For LevelMasters with boards whose firmware version is 7.000, use the commands listed in
b. Table
13.
10. Press
Enter
on the keyboard after the command has been typed.